AdiaPure

Settings reference

Every setting you can change, what it does, what it defaults to, and which values it accepts.

This page lists every setting you can change, what it does, what it defaults to, and which values it accepts.

Where settings live

SurfaceWhat you can change there
ScreenMost operating settings, plus the screen's own brightness, timeout and language
Web interfaceThe same operating settings, in the Configuration tab
Modbus and BACnetEverything, including the tuning parameters

A setting changed on the screen or in the web interface is written to the controller and stored in its non-volatile memory. A setting changed over the fieldbus is only live in memory until it is saved — see Maintenance and updates.

Values in the tables below are given in the unit the controller uses.

Operation

SettingWeb interface labelWhat it doesDefaultAllowed values
Operating modeOperation ModeStandby, Automatic or TestStandbyStandby, Automatic, Test
Number of tubesModbus onlyNumber of atomisation stages the unit has40–4
Master enable—Read-only. Active when the master-enable input is active——
Hygrostat—Read-only. Active when the hygrostat input is active——
Airflow—Read-only. Active when the airflow input is active——

Demand and humidity

SettingWeb interface labelWhat it doesDefaultAllowed values
Demand input modeDemand input modeWhere the demand comes from0-10V demand0-10V demand, 4-20mA demand, On/Off, External demand register, Return humidity voltage, Return humidity current
Desired return humidityReturn humidity setpointSetpoint used in the two return-humidity modes. Settable from the screen, the web interface and the fieldbus. The web interface only shows the field when the demand source is one of those two modes0 %0–100 %
External demand—Demand written from the fieldbus; only used with External demand register0 %0–100 %
Measured output humidity—Read-only humidity behind the unit, used by the limiter——
High-limit transmitter thresholdHighlimit transmitter thresholdOutput humidity above which the limiter cuts the demand60 %0–100 %
High-limit transmitter gainHighlimit transmitter gainHow sharply the limiter cuts the demand7.0any value

Water quality

SettingWeb interface labelWhat it doesDefaultAllowed values
Water temperature thresholdWater temperature thresholdWater temperature above which the water-temperature alarm is raised20 °C0 °C and above
Conductivity thresholdConductivity thresholdConductivity above which the conductivity alarm is raised40 µS/cm0 µS/cm and above

Flushing

SettingWeb interface labelWhat it doesDefaultAllowed values
Flush intervalFlush intervalHours between automatic flush cycles24 h0–48 h
Flush durationFlush durationSeconds each valve is held open during a flush30 s0–300 s
Next flush in—Read-only countdown to the next flush——

Outputs

SettingWeb interface labelWhat it doesDefaultAllowed values
Status output modeStatus output modeWhether the status relay rests open or closedNormally OpenNormally Open, Normally Closed
Alarm output modeAlarm output modeWhether the alarm relay rests open or closedNormally OpenNormally Open, Normally Closed
Aux 1 contact modeAux 1 contact modeWhether auxiliary 1 rests open or closedNormally OpenNormally Open, Normally Closed
Aux 2 contact modeAux 2 contact modeWhether auxiliary 2 rests open or closedNormally OpenNormally Open, Normally Closed
Aux 1 alarm maskAux 1 alarm maskWhich alarms switch auxiliary 1none selectedany combination of the 16 alarms
Aux 2 alarm maskAux 2 alarm maskWhich alarms switch auxiliary 2none selectedany combination of the 16 alarms
Analog outputAnalog outputWhat the 4–20 mA output carriesDemand input pinDemand input pin, External demand, Output humidity, Return humidity, Demand (post limiter), Water pressure (pre pump), Water pressure (post pump)

Network

SettingWeb interface labelWhat it doesDefaultAllowed values
DHCPDHCPGet the address from the network instead of using a fixed oneoffon / off
Static IPStatic IPThe fixed address to use192.168.1.195any IPv4 address
SubnetSubnet prefixThe subnet, as a prefix length240–32
GatewayGatewayThe default router192.168.1.1any IPv4 address

Fieldbus

SettingWeb interface labelWhat it doesDefaultAllowed values
RS-485 protocolRS485 protocolWhat the fieldbus carriesModbus RTUModbus RTU, BACnet MS/TP
RS-485 baud rateRS485 baud rateSpeed of the RS-485 bus1152009600–115200
BACnet/IP portBACnet/IP portUDP port for BACnet/IP478080–65535
BACnet MS/TP MACBACnet MS/TP MACNode address on the BACnet MS/TP bus10–127
BACnet device IDBACnet device IDDevice instance number, used by both BACnet/IP and BACnet MS/TP1any value
Modbus IDModbus IDNode address on the Modbus bus11–247
Modbus portModbus portTCP port for Modbus/TCP5020–65535

Test and maintenance

SettingWhereWhat it doesDefaultAllowed values
Test run demandScreen, ModbusDemand used while in Test mode100 %0–100 %
Test run durationScreen, ModbusSeconds the test runs before the unit returns to Standby1800 sany value
MaintenanceModbusAcknowledges that maintenance has been done. Resets the pump-hours counter and restarts the one-year countdownnot setset to 1

Tuning parameters

These are not on the screen or in the web interface. They are set over Modbus and BACnet.

Control loop

SettingWhat it doesDefaultAllowed values
PWM periodLength of the control cycle, in milliseconds10000 ms1–30000 ms
Pump spin-up timeTime the controller waits before it trusts the motor current reading, in milliseconds2000 msany value
P gainProportional gain of the return-humidity loop1.0any value
P limitLimit on the contribution of the P term1.0any value
I gainIntegral gain of the return-humidity loop0.0any value
I limitLimit on the contribution of the I term1.0any value
D gainDerivative gain of the return-humidity loop0.0any value
D limitLimit on the contribution of the D term1.0any value
Max off cyclesNumber of cycles with a control output of zero before the integrator is reset0 (disabled)any value
Valve 1 hysteresisKeeps valve 1 at its minimum duty cycle until the demand drops below the start threshold minus this value0.00–1 (0–100 %)

Valve steps

Each of the four valves has four settings. The values are fractions of the demand: 0.1 means 10 %.

SettingWhat it doesValve 1Valve 2Valve 3Valve 4
Lower levelDemand at which the valve starts to open0.10.50.00.0
Upper levelDemand at which the valve is fully open0.51.00.00.0
PWM startSmallest duty cycle the valve uses0.20.20.20.2
PWM endLargest duty cycle the valve uses0.80.80.80.8

A valve whose lower level is equal to or higher than its upper level never opens, and is skipped during flushing.

Conductivity probe

SettingWhat it doesDefaultAllowed values
Probe cell constantThe probe's cell constant, in 1/cm1.0any value
Probe temperature coefficientThe probe's temperature coefficient, in %/°C0.02any value
Probe offsetA static offset added to the measured conductivity, in µS/cm0.0any value
Probe NTC resistanceThe probe's NTC resistance at 25 °Cnot setany value
Probe NTC B valueThe probe's NTC B value3850any value
Prefer low measurement pathBiases the first measurement after start-up towards the low rangeoffon / off

Screen settings

These live in the screen itself and are not stored in the controller.

SettingWhereWhat it doesDefaultAllowed values
BrightnessSettings → Display SettingsScreen backlight level100 %10–100 %
Display timeoutSettings → Display SettingsHow long the screen stays on when idle5 minNever, 30 sec, 1 min, 2 min, 5 min, 10 min, 30 min, 1 hour
LanguageSettings → Display SettingsScreen languageEnglishEnglish, Nederlands, Français, Deutsch, Español

Settings that are fixed in the firmware

These values are not adjustable. The two pressure thresholds are part of the pump's safety behaviour, so they are deliberately not exposed as settings.

ValueThreshold
Inlet pressure alarm0.5 bar
Pump pressure alarm7.0 bar

Retired settings

SettingWhat happens
Measured output humidity enable (register 109)Retired. The firmware always reads the high-limit transmitter, and writes to this register have no effect

Settings that are read-only

These values are measured or counted by the controller. You can read them, but you cannot write them (except where noted).

Web interface labelWhat it is
Demand input pinThe demand read from the analogue input
Master enable, Hygrostat, AirflowThe state of the three enable inputs
Pump, Pressure low, Pressure highPump state and the two pressure readings
Motor currentThe measured motor current
Motor temperatureWhether the motor is over temperature
Water temperature, Board temperatureThe two temperature readings
ConductivityThe measured water conductivity
Analog outThe value currently on the 4–20 mA output
Valve 1–4, Flush valveThe open/closed state of each valve
Flush inputWhether the external flush input is active
Total pump hours, Pump hours left, Maintenance inMaintenance counters
Motor starts, Valve 1–4 starts, Flush valve startsStart counters
Tubes, RebootsUnit configuration and the boot counter
Active alarms, Alarm logThe alarm state and the alarm history

Next steps